This document specifies:
- the test conditions and test methods for determining capacity and efficiency ratings;
- calculation methods for seasonal performance.
This applies to factory made, electric mains operated, variable refrigerant flow air-cooled air conditioners and air-to-air heat pumps with a rated capacity above 12 kW for cooling or for heating if the product has no cooling function.
In this document, “heat pumps” means “air-to-air heat pumps” and “air conditioners” means “air-cooled air conditioners”.
This document establishes a method for determining global variable refrigerant flow (VRF) performance with annexes addressing specific national or regional deviations, such as regionally specific power or testing requirements.
This document does not apply to the testing and rating of:
- water-source heat pumps or water-cooled air conditioners;
- multi-split systems where each indoor unit has dedicated piping connected directly to the outdoor unit;
- individual assemblies not constituting a complete refrigeration system.
Общая информация
-
Текущий статус: ОпубликованоДата публикации: 2026-02Этап: Опубликование международного стандарта [60.60]
-
Версия: 1
-
Технический комитет :ISO/TC 86/SC 6
- RSS обновления
Жизненный цикл
-
Сейчас
-
00
Предварительная стадия
-
10
Стадия, связанная с внесением предложения
-
20
Подготовительная стадия
-
30
Стадия, связанная с подготовкой проекта комитета
-
40
Стадия, связанная с рассмотрением проекта международного стандарта
-
50
Стадия, на которой осуществляется принятие стандарта
-
60
Стадия, на которой осуществляется публикация
-
90
Стадия пересмотра
-
95
Стадия, на которой осуществляется отмена стандарта
-
00